이 문서에서는 일반적인 목적으로 BBU(Battery Backup Unit)의 배터리 수명을 확인하는 방법에 대해 설명합니다. 또는 다음과 유사한 이벤트를 수신한 경우:
Warning battery: The battery backup unit in chassis XXXXXXXXXXXXXX slot 2 has indicated cell End Of Life. Replace the battery backup unit as soon as possible.
필수 구성 요소:
클러스터에서 상태 점검 프레임워크 35 이상 및 다음 OneFS 버전 중 하나를 실행해야 합니다.
# isi healthcheck version HealthCheck definition version: 35.0.0
# isi healthcheck run battery_test_status -v Queued evaluation to run: battery_test_status20231011T1718
isi healthcheck list | grep battery_test_status20231011T1718 Completed - Pass - /ifs/.ifsvar/modules/health-check/results/evaluations/battery_test_status20231011T1718
# cat /ifs/.ifsvar/modules/health-check/results/evaluations/battery_test_status20231011T1718 {"checklist_id": "battery_test_status", "delivery": [], "id": "battery_test_status20231011T1718", "overrides": [], "parameters": {}, "start_time": 1697044712.9590354} {"name": "battery_test_status", "parameters": {}, "status": "OK", "value": 100, "details": ["Battery 1 has 0 most recent test failures, threshold is 3", "Battery 1 Permanent fault status is False", "Battery 1 Capacity Degradation: 137600 mAh, 13.1%"], "node": "1", "passed": true} {"name": "battery_test_status", "parameters": {}, "status": "OK", "value": 100, "details": ["Battery 1 has 0 most recent test failures, threshold is 3", "Battery 1 Permanent fault status is False", "Battery 1 Capacity Degradation: 136100 mAh, 12.96%"], "node": "2", "passed": true} {"name": "battery_test_status", "parameters": {}, "status": "OK", "value": 100, "details": ["Battery 1 has 0 most recent test failures, threshold is 3", "Battery 1 Permanent fault status is False", "Battery 1 Capacity Degradation: 136850 mAh, 13.03%"], "node": "3", "passed": true} {"name": "battery_test_status", "parameters": {}, "status": "OK", "value": 100, "details": ["Battery 1 has 0 most recent test failures, threshold is 3", "Battery 1 Permanent fault status is False", "Battery 1 Capacity Degradation: 136400 mAh, 12.99%"], "node": "4", "passed": true} {"result":"PASS"}
isi upgrade cluster firmware devices | egrep "mongoose|bcc"
명령의 출력은 다음과 같습니다.
# isi upgrade cluster firmware devices| egrep "mongoose|bcc" MLKbem_mongoose ePOST 02.40 1-4 EPbcc_infinity ePOST 02.40 5-8
BBU 펌웨어는 40% 성능 저하에서 50% 성능 저하로 전환되는 시간에 영향을 미칩니다.
BBU 펌웨어 버전이 1.20인 경우 배터리가 40%에서 50%로 저하되는 데 4개월이 걸립니다.
BBU 펌웨어 버전이 2.20 이상인 경우 배터리가 40%에서 50%로 저하되는 데 12개월이 걸립니다.
BBU 펌웨어 버전 1.20 이하가 설치되어 있고 지원되는 최신 펌웨어로 업그레이드하려면 먼저 다음 문서를 검토해야 합니다. 노드 펌웨어 패키지 10.3.9 또는 11.6으로 업그레이드하기 전에 배터리 테스트를 수행하는 방법