Dell PowerEdge R7515 Installation and Service Manual

Removing the heat sink

Prerequisites

  1. Follow the safety guidelines listed in the Safety instructions.
  2. Follow the procedure listed in the Before working inside your system.
  3. Remove the air shroud.
NOTE: The heat sink and processor are too hot to touch for some time after the system has been powered down. Allow the heat sink and processor to cool down before handling them.

Steps

  1. Using a Torx #T20 screwdriver, loosen the captive screws in the order mentioned on the heat sink:
    NOTE:The captive screw numbers are marked on the heat sink.
    1. Partially loosen the captive screws 1 and 2 (approximately 3 turns).
    2. Partially loosen the captive screws 3 and 4 (approximately 3 turns).
    3. Loosen the captive screws 1 and 2 completely.
    4. Loosen the captive screws 3 and 4 completely.
  2. Lift the heat sink from the system.
    Figure 1. Removing the heat sink

    This image shows how to remove the heat sink.

Next steps

  1. If you are removing a faulty heat sink, replace the heat sink, if not, remove the processor.