The PowerEdgeR760system supports up to two AC or DC power supply units (PSUs).

Table 1. PSU specifications This table describes PSU specifications for the system.
PSU Class Heat dissipation (maximum) (BTU/hr) Frequency (Hz) AC Voltage DC Voltage Current (A)
200—240 V 100—120 V 277 V 240 V - (48—60) V 336 V
700 W mixed mode HLAC Titanium 2625 50/60 700 W N/A N/A N/A N/A N/A 4.1
N/A 2625 N/A N/A N/A N/A 700 W N/A N/A 3.4
800 W mixed mode Platinum 3000 50/60 800 W 800 W N/A N/A N/A N/A 9.2—4.7
N/A 3000 N/A N/A N/A N/A 800 W N/A N/A 3.8
1100 W mixed mode Titanium 4100 50/60 1100 W 1050 W N/A N/A N/A N/A 12—6.3
N/A 4100 N/A N/A N/A N/A 1100 W N/A N/A 5.2
1400 W mixed mode Platinum 5250 50/60 1400 W 1050 W N/A N/A N/A N/A 12—8
N/A 5250 N/A N/A N/A N/A 1400 W N/A N/A 6.6
1400 W mixed mode 277 Vac and HVDC Titanium 5250 50/60 N/A N/A 1400 W N/A N/A N/A 5.8
5250 N/A N/A N/A N/A N/A N/A 1400 W 5.17
1800 W mixed mode HLAC Titanium 6750 50/60 1800 N/A N/A N/A N/A N/A 10
N/A 6750 N/A N/A N/A N/A 1800 W N/A N/A 8.2
2400 W mixed mode Platinum 9000 50/60 2400 W 1400 W N/A N/A N/A N/A 16—13.5
N/A 9000 N/A N/A N/A N/A 2400 W N/A N/A 11.2
2800 W mixed mode HLAC Titanium 10500 50/60 2800 W N/A N/A N/A N/A N/A 15.6
N/A 10500 N/A N/A N/A N/A 2800 W N/A N/A 13.6
1100 W -48 V DC N/A 4265 N/A N/A N/A N/A N/A 1100 W N/A 27
3200 W mixed mode 277 Vac and HVDC Titanium 12000 50/60 N/A N/A 3200 W N/A N/A N/A 13
12000 N/A N/A N/A N/A N/A N/A 3200 W 11.5
NOTE:Heat dissipation is calculated using the PSU wattage rating.
NOTE:When selecting or upgrading the system configuration, to ensure optimum power utilization, verify the system power consumption with the Enterprise Infrastructure Planning Tool available at Dell.com/calc.
NOTE:If a system with AC 2400 W PSUs operates at low line 100-120 Vac, then the power rating per PSU is degraded to 1400 W.
NOTE:If a system with AC 1400 W or 1100 W PSUs operates at low line 100-120 Vac, then the power rating per PSU is degraded to 1050 W.
NOTE:
  • HLAC stands for High-Line AC, with a range of 200 - 240 V AC.
  • HVDC stands for High-Voltage DC, with 336 V DC.
Figure 1. PSU power cables
this image shows list of PSU power cords
Figure 2. APP 2006G1 power cable

this image shows list of PSU power cord

Table 2. PSU power cablesThe table lists the PSU power cables list .
Form factor Output Power cable
Redundant 60 mm 700 W mixed mode HLAC C13
800 W mixed mode C13
1100 W mixed mode C13
1400 W mixed mode C13
1400 W mixed mode 277 Vac and HVDC APP 2006G1
1800 W mixed mode HLAC C15
Redundant 86 mm 2400 W mixed mode C19
2800 W mixed mode HLAC C21
3200 W mixed mode 277 Vac and HVDC APP 2006G1
NOTE:C19 power cable combined with C20 to C21 jumper power cable can be used to adapt 2800 W PSU.