NOTE:For
additional information about environmental measurements for specific
system configurations, see Dell.com/environmental_datasheets.
Temperature
Specifications
Continuous operation (for altitude less than 950 m
or 3117 ft)
10 °C to 35 °C (50 °F to 95 °F) with no direct sunlight
on the equipment.
Maximum temperature gradient (operating and storage)
20 °C/h (36 °F/h)
Storage temperature limits
–40 °C to 65 °C (–40 °F to 149 °F)
Relative humidity
Specifications
Storage
5% to 95% RH with 33 °C (91 °F) maximum dew point.
Atmosphere must be non-condensing at all times.
Operating
10% to 80% Relative Humidity with 26 °C (78.8 °F)
maximum dew point.
Maximum vibration
Specifications
Operating
0.26 Grms at 5 Hz to 350 Hz (all operation orientations).
Storage
1.87 Grms at 10 Hz to 500 Hz for 15 min (all six
sides tested).
Maximum shock
Specifications
Operating
One shock pulse in the positive z axis of 31 G for
2.6 ms in all operational orientations.
Storage
Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of the system)
of 71 G for up to 2 ms.
Maximum altitude
Specifications
Operating
3,048 m (10,000 ft)
Storage
12,000 m (39,370 ft).
Operating Altitude De-rating
Specifications
Up to 35 °C (95 °F)
Maximum temperature is reduced by 1 °C/300 m (1 °F/547
ft) above 950 m (3,117 ft).
35 °C to 40 °C (95 °F to 104 °F)
Maximum temperature is reduced by 1 °C/175 m (1 °F/319
ft) above 950 m (3,117 ft).
40 °C to 45 °C (104 °F to 113 °F)
Maximum temperature is reduced by 1 °C/125 m (1 °F/228
ft) above 950 m (3,117 ft).
The following section defines the limits to help
avoid IT equipment damage and/or failure from particulates and gaseous
contamination. If it is determined that levels of particulates or
gaseous pollution are beyond the limits specified below and are the
reason for the damage and/or failures to your equipment, it may be
necessary for you to re-mediate the environmental conditions that
are causing the damage and/or failures. Re-mediation of environmental
conditions will be the responsibility of the customer.
Particulate contamination
Specifications
Air filtration
Data center air filtration as defined by ISO Class
8 per ISO 14644-1 with a 95% upper confidence limit.
NOTE:Applies to data center
environments only. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in environments
such as an office or factory floor.
NOTE:Air entering the data
center must have MERV11 or MERV13 filtration.
Conductive Dust
Air must be free of conductive dust, zinc whiskers,
or other conductive particles.
NOTE:Applies to data center
and non-data center environments.
Corrosive Dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
NOTE:Applies
to data center and non-data center environments.
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Silver coupon corrosion rate
<200 Å/month as defined by AHSRAE TC9.9.
NOTE:Maximum
corrosive contaminant levels measured at ≤50% relative humidity.