Power requirements vary depending on system configuration, loading, and environmental conditions. The table below describes the maximum expected power draw. To estimate power consumption values for your specific environment, use the
Dell Power Calculator.
Table 1. Power requirements for x000 modelsColumn one lists the requirements, and the other columns list the x000 models.
Requirement
1000T
3000T
5000T
7000T
9000T
Maximum input power
240 VAC ± 10%, single phase
For 100-120V, a customer-supplied step-up transformer is required.
AC Line Current (operating maximum at 200 VAC)
6.7 A
8.1 A
9.0 A
9.3 A
10.4 A
Power Consumption (operating maximum at 200 VAC)
1385 VA (1316 W)
1629.6 VA (1597 W)
1792.9 VA (1757 W)
1868.4 VA (1831 W)
2088.8 VA (2047 W)
Heat Dissipation (operating maximum)
4.73 x 106 J/hr, (4,490 Btu/hr)
5.74 x 106 J/hr, (5,449 Btu/hr)
6.32 x 106 J/hr, (5,995 Btu/hr)
6.59 x 106 J/hr, (6,248 Btu/hr)
7.37 x 106 J/hr, (6,985 Btu/hr)
AC Inlet type
IEC320-C14 or IEC320-C20 appliance coupler per power zone
IEC320-C20 appliance coupler per power zone
Normal input frequency
47 Hz–63 Hz
Maximum inrush current
45 Apk "cold" per line cord at any line voltage
AC protection
20 A fuse on each power supply, single line
Ride-through time
10 ms min
Current sharing
± 5 percent of full load between power supplies
Startup Surge Current
120 Apk "hot" per line cord, at any line voltage
Table 2. Power requirements for x200 modelsColumn one lists the requirements, and the other columns list the x200 models.
Requirement
1200T
3200T
3200Q
5200T
9200T
Maximum input power
240 VAC ± 10%, single phase
For 100-120V, a customer-supplied step-up transformer is required.
AC Line Current (operating maximum at 200 VAC)
6.5 A
7.1 A
7.7 A
8.8 A
9.8 A
Power Consumption (operating maximum at 200 VAC)
1297.2 VA (1271.3 W)
1422 VA (1393.6 W)
1535.8 VA (1505.1 W)
1769.8 VA (1734.4 W)
1958.6 VA (1919.4 W)
Heat Dissipation (operating maximum)
4.58 x 106 J/hr, (4,338 Btu/hr)
5.02 x 106 J/hr, (4,755 Btu/hr)
5.42 x 106 J/hr, (5,136 Btu/hr)
6.24 x 106 J/hr, (5,918 Btu/hr)
6.91 x 106 J/hr, (6,549 Btu/hr)
AC Inlet type
IEC320-C14 or IEC320-C20 appliance coupler per power zone
IEC320-C20 appliance coupler per power zone
Normal input frequency
47 Hz–63 Hz
Maximum inrush current
45 Apk "cold" per line cord at any line voltage
AC protection
20 A fuse on each power supply, single line
Ride-through time
10 ms min
Current sharing
± 5 percent of full load between power supplies
Startup Surge Current
120 Apk "hot" per line cord, at any line voltage
Table 3. High ambient temperature shutdownColumn one lists the ambient temperature, and the other columns list the hardware faults and consequences.
Ambient temperature
Hardware fault
Consequence
Above 45° C (113° F)
None
Noncritical warning generated.
Above 50° C (122° F)
None
Critical alert generated. The system shuts down after five minute timer expires. If the temperature returns to less than 45° C (113° F) , the system powers on.
Any
Three hottest drives have an average temperature of 50° C (122° F)
The system shuts down after five minute timer expires.
Any
Two fans fault
The system shuts down after five minute timer expires.