Power requirements for the NVMe expansion enclosure
Power requirements vary depending on system configuration, loading, and environmental conditions. The table below describes the maximum expected power draw. To estimate power consumption values for your specific environment, use the
Dell Power Calculator.
Table 1. Power requirementsColumn one lists the requirements, and column two provides descriptions.
Requirement
Description
AC line voltage
100 to 240 VAC +/- 10%, single-phase, 47 to 63 Hz
AC line current (operating maximum)
6.49 A max at 100 VAC
3.31 A max at 200 VAC
Power consumption (operating maximum at 200 VAC)
663 VA (630 W)
Power factor
0.92 minimum at full load 100V/200V
Heat dissipation (operating maximum at 200 VAC)
2.27 x 106 J/hr (2,150 Btu/hr)
In-rush current
82A max for 1/2 Line cycle per line cord at 200 VAC
Startup surge current
100A Max for up to 125uSec
AC protection
15 A fuse on each power supply, both Line and Neutral
AC inlet type
IEC320-C14 appliance coupler, per power zone
Ride-through time
10-millisecond minimum
Current sharing
+/- 5% of full load between power supplies