NOTE: For additional information
about environmental measurements for specific system configurations,
see Dell.com/environmental_datasheets.
Temperature
Specifications
Storage
–40°C to 65°C (–40°F to 149°F)
Continuous operation (for altitude less than 950
m or 3117 ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight
on the equipment.
Fresh air
For information on fresh air, see Expanded Operating
Temperature section.
Maximum temperature gradient (operating and storage)
20°C/h (68°F/h)
Relative humidity
Specifications
Storage
5% to 95% RH with 33°C (91°F) maximum dew point.
Atmosphere must be non-condensing at all times.
Operating
10% to 80% Relative Humidity with 29°C (84.2°F) maximum
dew point.
Maximum vibration
Specifications
Operating
0.26 Grms at 5 Hz to 350 Hz (operation
orientation).
Storage
1.88 Grms at 10 Hz to 500 Hz for 15 min
(all six sides tested).
Maximum shock
Specifications
Operating
Six consecutively executed shock pulses in the positive
and negative x, y, and z axes of 40 G for up to 2.3 ms.
Storage
Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of the system)
of 71 G for up to 2 ms.
Maximum altitude
Specifications
Operating
30482000 m (10,0006560 ft).
Storage
12,000 m (39,370 ft).
Operating temperature de-rating
Specifications
Up to 35 °C (95 °F)
Maximum temperature is reduced by 1°C/300 m (33.8°F/984.25
ft) above 950 m (3,117 ft)
35 °C to 40 °C (95 °F to 104 °F)
Maximum temperature is reduced by 1°C/175 m (1°F/574.14
ft) above 950 m (3,117 ft).
40 °C to 45 °C (104 °F to 113 °F)
Maximum temperature is reduced by 1°C/125 m (1°F/410.1
ft) above 950 m (3,117 ft).
The following section defines the limits to help
avoid IT equipment damage and/or failure from particulates and gaseous
contamination. If the levels of particulates or gaseous pollution
are beyond the specified limits and cause equipment damage or failure,
you may need to rectify the environmental conditions. Remediation
of environmental conditions is the responsibility of the customer.
Particulate contamination
Specifications
Air filtration
Data center air filtration as defined by ISO Class
8 per ISO 14644-1 with a 95% upper confidence limit.
NOTE: Applies to data center
environments only. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in environments
such as an office or factory floor.
NOTE: Air entering the data
center must have MERV11 or MERV13 filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers,
or other conductive particles.
NOTE: Applies to data center
and non-data center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
NOTE: Applies
to data center and non-data center environments.
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Silver coupon corrosion rate
<200 Å/month as defined by AHSRAE TC9.9.
NOTE: Maximum
corrosive contaminant levels measured at ≤50% relative humidity.