Ambient temperature limitations

The following table lists configurations that require ambient temperature less than 35°C.

NOTE The ambient temperature limit must be adhered to ensure proper cooling and to avoid excess CPU throttling, which may impact system performance.
Table 1. Configuration based ambient temperature restrictionsThe following table lists configurations that require ambient temperature less than 35°C.
Storage configuration Chassis or hardware configuration CPU Thermal Design Power (TDP) CPU heat sink Fan type Ambient restriction

12 x 3.5 inch

Mid (SAS) and rear drive 200 W/180 W 1U high performance High performance 30°C

12 x 3.5 inch

Mid (SAS) and rear drive 120-170 W 1U standard High performance 35°C

24 x 2.5 inch

Mid (SAS) and rear drive All

1U high performance for 180/200W

1U standard for 120-170W

High performance 35°C

24 x 2.5 inch

All PCIe cards 200 W/180 W 2U Standard 35°C

12 x 3.5 inch

All PCIe cards 200 W/180 W 2U Standard 35°C

8 x 3.5 inch

All PCIe cards 200 W/180 W 2U Standard 35°C

24 NVMe

All PCIe cards 200 W/180 W 2U Standard 35°C