Environmental requirements
The following tables list the environmental requirements for a solution
with different configurations of:
- 14 GB SUs
- 200-volt AC input voltage
- 35°C maximum ambient
temperature
Table 1. GPU environmental requirementsGPU environmental requirements
Object
|
4-node
|
8-node
|
Watts
|
BTU/hr
|
Watts
|
BTU/hr
|
NVIDIA V100s GPU
|
Input power
|
7,159
|
24,400
|
13,391
|
45,600
|
Input current (amps) at 200 VIN
|
35.8
|
68.0
|
Weight
|
880 lbs (399 kg)
|
1,204 lbs (546 kg)
|
AMD Mi25 GPU
|
Input power
|
7,159
|
24,400
|
13,391
|
45,600
|
Input current (amps) at 200 VIN
|
35.8
|
68.0
|
Weight
|
880 lbs (399 kg)
|
1,204 lbs (546 kg)
|
NVIDIA T4 GPU
|
Input power
|
4009
|
13,679
|
6,621
|
22,591
|
Input current (amps) at 200 VIN
|
18.4
|
30.0
|
Weight
|
880 lbs (399 kg)
|
1,204 lbs (546 kg)
|
Table 2. Dense configuration environmental requirementsDense configuration environmental requirements
Object
|
4-node
|
8-node
|
12-node
|
16-node
|
Watts
|
BTU/hr
|
Watts
|
BTU/hr
|
Watts
|
BTU/hr
|
Watts
|
BTU/hr
|
Input power
|
5,630
|
19,200
|
10,411
|
35,500
|
15,161
|
51,700
|
19,941
|
68,000
|
Input current (amps)
at 200 VIN
|
28.4
|
52.4
|
76.4
|
100.4
|
Weight
|
880 lbs (399 kg)
|
1204 lbs (546 kg)
|
1,593 lbs (693 kg)
|
2301 lbs (1,044 kg) 2 racks
|
Table 3. Hybrid configuration environmental requirementsHybrid configuration environmental requirements
Object
|
4-node
|
8-node
|
12-node
|
16-node
|
Watts
|
BTU/hr
|
Watts
|
BTU/hr
|
Watts
|
BTU/hr
|
Watts
|
BTU/hr
|
Input power
|
Min config.
|
3,395
|
11,577
|
5,979
|
20,388
|
8,563
|
29,200
|
11,147
|
38,011
|
Mid config.
|
3,691
|
12,586
|
6,571
|
22,407
|
9,451
|
32,228
|
12,331
|
42,049
|
Max config.
|
3,927
|
13391
|
7,043
|
24,017
|
10,159
|
34,642
|
13,275
|
45,268
|
Input current (amps)
|
Min config.
|
17.2
|
30.3
|
43.4
|
56.5
|
Mid config.
|
18.7
|
33.3
|
47.8
|
62.4
|
Max config.
|
19.9
|
35.6
|
51.4
|
67.1
|
Weight
|
790 lbs (358 kg)
|
1,082 lbs (491 kg)
|
1,374 lbs (623 kg)
|
1,666 lbs (756 kg)
|
Table 4. All-flash configuration environmental requirementsAll-flash configuration environmental requirements
Object
|
4-node
|
8-node
|
12-node
|
16-node
|
Watts
|
BTU/hr
|
Watts
|
BTU/hr
|
Watts
|
BTU/hr
|
Watts
|
BTU/hr
|
Input power
|
Min config.
|
2,620
|
8,800
|
4,360
|
14,600
|
6,090
|
20,400
|
7,830
|
26,200
|
Max config.
|
3,410
|
11,500
|
5,930
|
20,000
|
8,460
|
28,500
|
10,980
|
37,100
|
Input current (amps)
|
Min config.
|
13.1
|
21.8
|
30.5
|
39.7
|
Max config.
|
17.05
|
29.7
|
42.3
|
54.9
|
Weight
|
703 lbs (319 kg)
|
899 lbs (408 kg)
|
1,096 lbs (497 kg)
|
1,292 lbs (586 kg)
|
Data is not available for the Topic