The following table describes the particulate contamination specifications:
Particulate contamination | Specifications |
---|---|
Air filtration | Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
This condition applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor. Air filtering can also be accomplished by filtering room air with MERV8 filter per ANSI/ASHRAE Standard 127. NOTE:Air entering the data center must have MERV11 or MERV13 filtration.
|
The following table describes the gaseous contamination specifications:
Gaseous contamination | Specifications |
---|---|
Copper Coupon Corrosion rate | <300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013 |
Silver Coupon Corrosion rate | <200 Å/month as defined by ANSI/ISA71.04-2013 |