Bu belgede, pil yedekleme ünitesinin (BBU) pil ömrünün genel amaçlar için nasıl kontrol edileceği anlatılmaktadır veya buna benzer bir olay aldıysanız aşağıdakileri yapın:
Warning battery: The battery backup unit in chassis XXXXXXXXXXXXXX slot 2 has indicated cell End Of Life. Replace the battery backup unit as soon as possible.
Önkoşul:
Küme, Sistem Durumu Denetimi Çerçevesi 35 veya sonraki bir sürümünü ve OneFS'nin aşağıdaki sürümlerinden birini çalıştırıyor olmalıdır:
# isi healthcheck version HealthCheck definition version: 35.0.0
# isi healthcheck run battery_test_status -v Queued evaluation to run: battery_test_status20231011T1718
isi healthcheck list | grep battery_test_status20231011T1718 Completed - Pass - /ifs/.ifsvar/modules/health-check/results/evaluations/battery_test_status20231011T1718
# cat /ifs/.ifsvar/modules/health-check/results/evaluations/battery_test_status20231011T1718 {"checklist_id": "battery_test_status", "delivery": [], "id": "battery_test_status20231011T1718", "overrides": [], "parameters": {}, "start_time": 1697044712.9590354} {"name": "battery_test_status", "parameters": {}, "status": "OK", "value": 100, "details": ["Battery 1 has 0 most recent test failures, threshold is 3", "Battery 1 Permanent fault status is False", "Battery 1 Capacity Degradation: 137600 mAh, 13.1%"], "node": "1", "passed": true} {"name": "battery_test_status", "parameters": {}, "status": "OK", "value": 100, "details": ["Battery 1 has 0 most recent test failures, threshold is 3", "Battery 1 Permanent fault status is False", "Battery 1 Capacity Degradation: 136100 mAh, 12.96%"], "node": "2", "passed": true} {"name": "battery_test_status", "parameters": {}, "status": "OK", "value": 100, "details": ["Battery 1 has 0 most recent test failures, threshold is 3", "Battery 1 Permanent fault status is False", "Battery 1 Capacity Degradation: 136850 mAh, 13.03%"], "node": "3", "passed": true} {"name": "battery_test_status", "parameters": {}, "status": "OK", "value": 100, "details": ["Battery 1 has 0 most recent test failures, threshold is 3", "Battery 1 Permanent fault status is False", "Battery 1 Capacity Degradation: 136400 mAh, 12.99%"], "node": "4", "passed": true} {"result":"PASS"}
isi upgrade cluster firmware devices | egrep "mongoose|bcc"
Komutun çıktısı şöyle görünür:
# isi upgrade cluster firmware devices| egrep "mongoose|bcc" MLKbem_mongoose ePOST 02.40 1-4 EPbcc_infinity ePOST 02.40 5-8
BBU bellenimi, %40 performans düşüşünden %50 performans düşüşüne geçmek için gereken süreyi etkiler.
BBU bellenim sürümü 1.20 ise pilin %40'tan %50 ye düşmesi dört ay sürecektir.
BBU bellenim sürümü 2.20 veya üzeriyse pilin %40'tan %50 ye düşmesi 12 ay sürecektir.
BBU bellenim sürümü 1.20 veya daha eski bir sürüm yüklüyse ve desteklenen en son bellenime yükseltmek istiyorsanız öncelikle bu belgeyi incelemeniz gerekir: Düğüm Bellenim Paketi 10.3.9 veya 11.6'ya yükseltmeden önce pil testini gerçekleştirme